Bookmark Mail this page Print this page
QUICK LINKS

ELECTRICAL (TD)                         

·ORGANISATION

Gazetted-                 Sr.DEE (TD)                       -           Sh P.P.Sharma

                                 DEE/TD                   -           Sh R. K. Waghela

ADEE/TD/GWL       -           Sh Janardan Singh

ADEE/TD/LAR         -           Sh Ghanshyam Dass

ADEE/TD/OR          -           Sh Nagendra Tiwari

1.INTRODUCTION:

Jhansi division has electrified section from DHO (Excluding) to Bina (Excluding) (314.66 RKM & 840.52 TKM), JHS to GOY (230.57 RKM & 325.71TKM) & LAR to Udaipura (38.331 RKM & 66.87TKM) totaling 583.567 RKM & 1233.07TKM.

There are 09Traction sub stations, out of which 05 Traction Substations, Lalitpur, Mustara, Moth, Lalpur and Sarsoki get 132 KV incoming supply from DVVNL (UPPCL) and 04 Traction Substations namely Hetampur, Gwalior, Datia, Basai get 132 KV incoming supply from RGPPL/JIPTL through open access.

2.          Non-Gazetted – Sanctioned strength- 542Nos.

                                                          On Roll-431 Nos.

                                                          Vacancies-111 Nos.

   ASSETS / ACHEIVEMENT/ PERFORMANCE –

ASSETS:  -   Assets at a glance of TRD branch of JHS division are as under –

Sr.

No.

Details

Holding

M/L

CNB/L

Total

1.

Major Depots

4 (LAR,JHS,GWL,DHO)

1 (ORAI)

05

2.

Minor depots

3 (TBT,BAB,DBA)

2 (CGN,PHN)

05

3.

RKMs

353.491

230.57

584.061

4.

TKM

907.39

325.71

1233.1

5.

Crossovers

95

5

100

6.

Turnouts

636

173

809

7.

ATDs

1836

576

2412

8.

Isolators

253

121

374

9.

TSS’s

5

4

09

10.

SPs

6

4

10

11.

SSPs.

17

9

26

12.

Tower wagon

13     (4-8Wh & 9-4Wh)

13.

Power Transformer

17(each 21.6 MVA), 01(each 12.5 MVA)

 

3.  Performance indices –

S.No.

Parameters

15-16

16-17

17-18

1

OHE Failures (internal)

5

05

05

2

Punctuality Loss

10

63

18

4.   ERGY DETAILS –

4.1SEC -

YEAR

GOODS

PASSENGER

OVERALL

2015-16

6.33

18.03

10.14

2016-17

5.15

18.00

9.83

2017-18 (upto Dec-17)

4.82

17.98

10.16

   4.2          ENERGY COST & CONSUMPTION *-

Year

Last month(NDec)

Cumulative up to Dec

Total for the year

KWh

Bill             in Cr.

Per unit cost

KWh

Bill     in Cr.

Per unit cost

KWh

Bill       in Cr.

Per unit cost

2015-16

30152290

19.35

6.42

251746370

164.21

6.52

328951591

208.21

6.33

2016-17

30300529

16.97

5.60

249923988

137.34

5.50

337017387

184.57

5.48

2017-18 (upto Dec-17)

28496902

16.70

5.86

267218287

151.72

5.68

267218287

151.72

5.68

    

4.3            PER UNIT COST * –

YEAR

MPMKVV (Per unit Cost )

DVVNL (Per unit Cost )

RGPPL (Per unit Cost)

Combined Avg Per unit cost. (Open access + UP)

2015-16 

6.27

8.10

6.09

6.54

2016-17 

00

8.44

4.60

5.48

2017-18

(upto Dec-17)

00

8.99

4.57

5.68

5.        Saving in Energy bills:-

           Since 22.01.2016 at 12.00Hrs. supply of DAA, BZY & GWL/TSS and from 20.03.2016 at 24Hrs. supply of HET/TSS transferred from MPMKVV.Co.Ltd to  RGPPL through open access and debit for energy is being raised by WCR as open access bills are co-ordinated by WCR. In comparison to previous bills of MPMKVV with open access total saving due to low unit cost is-

Rs. 34,20,62,184/- has been saved from Apr-17 to Dec-17.

 6.        RELIABILITY MEASURES –

          For improving reliability of OHE, the following actions have being taken.

 

SN.

Action taken

Achievement Up to the month of  Jan-17

1

Replacement of S.S. Wire Rope

459 Nos.

2

Replacement of winch type ATDs with 3- pulley type ATDs.

347 Nos.

3

Replacement of flashed and broken insulators

419 Nos.

4

Provision of missing /disconnected OHE bonds

2119 Nos.

5

Replacement of “C” Jumpers

189 Nos.

6

Replacement of “G” jumpers

77 Nos.

7

Replacement of “Anti Theft Jumpers”

427 Nos.

8

Pruning of trees hazardous to OHE.

3497 Nos.

7.           EIG sanction work –

1.   2.2KV anti theft charging EIG sanction has been received for the section Jhansi (Excl.) to Harpalpur (Incl.) Km-1290/90.5 to 1214/376.

2.   25KV EIG sanction has been received for the section LAR (Excl.) to Udaipura(Incl.) Km-1039/282.50 to 1071/61.50 (RKM-32.0 & TKM-40.8) & section CRS was done on 05.08.17 and section commissioned on 04.09.17 .

3.   EIG sanction received of TR-26 (21.6/30.24MVA traction transformer) of CKT-II at LLR/TSS and transformer charged on dated 26.08.2017.

4.  EIG sanction received of TR-19 (21.6/30.24MVA traction transformer) of 

            CKT-I at MSV/TSS and TR taken on load on dated 17.07.17.

5.   EIG sanction received for the IGBT based fixed HT and dynamic reactive capacitor unit at HET/TSS & commissioned on dated 26.07.17.

6.   EIG for Parichha/SSP & OHE for JHS- Parichha thermal cabin section have been sanctioned on Dt: 09.8.17 (RKM-24.24, TKM-31.505) and section anti theft charging done on dt:03.02.18.

7.   EIG for one CKT TR-23 for Sarsoki/TSS and Power Transformer TR-23 & TR-24, 21.6/30.24MVA has been sanctioned on Dt: 23.8.17.

8.   EIG for AT provided on Level crossing gate & station yard for JHS- Parichha section have been sanctioned on Dt: 25.9.17.

9.   EIG sanction received of Udaipura-LPGCL yard on Dt: 11.10.17.

8.           Progress of RE & RVNL work –

1.LAR- Udaipura section electrification commissioned on Dt: 4.9.17.

2.Udaipura-LPGCL  yard electrification commissioned on dated 16.10.2017.

3.Electrification of X-over no. 121 between  UP main line to UDPR line  at LAR station has been completed & given fit for electric traffic on dated 17.10.17.

4.Sarsoki/TSS- One circuit commissioned on Dt: 15.9.17.

   9.        Others works completed –

  1. 566Nos.  high creepage  polluted zone insulator has been replaced at DCPG, PTPP and GWL polluted zone yard.
  2. 05Nos. AT has been replaced due to Low BDV of oil by LAR depot after centrifuging oil in depot.
  3. Tramway type OHE has been converted into conventional type OHE of PF no.4 & PF no.5 at JHS Yd.(730 mtrs.)
  4. 02 Nos. Aluminum cross feeder replaced by Copper feeder wire at SOR/SSP and 03 Nos. modified drop jumper also provided.
  5. To avoid 9 Tonne insulator failure of ATD (total 112 Nos. New double strap has been provided and total – 95 Nos. Tilted compensating plate has been rectified.
  6. At 17 Nos. locations insulated catenary has been replaced by contact wire under FOB/ROB at SOR/FOB, DAA/FOB and JHS/FOB. 

7.05Nos. Static Relays has been replaced by Numerical relays at BZY/TSS.

  1. 13 nos. Vacuum type BM of BHEL make replaced. (JHS/SP - 4 nos, CHN/SP –  1 no, ATA/SSP – 1 no, PHN/SSP – 1 no, BNAR/SSP – 1 no & PMN/SSP – 1 no, BZM/SP

04 nos)

9.17Nos. New battery set commissioned in place of old battery set in JHS Div.

  1. DAA Point No.-102A (Shunting neck) given fit on Dt: 23.11.17, which was unfit since last 7 years

10.Assistance required:-

  • Proposal for creation of 115 posts for Jhansi-Kanpur doubling was sent to HQrs.   Same may be expedited please.
  • Proposal for creation of 210 posts for Jhansi-Manikpur section including Khairar-Bhimsen has been sent to HQrs after Divisional Account’s vetting.  May be expedited please.




Source : North Central Railways / Indian Railways Portal CMS Team Last Reviewed on: 19-02-2018